Using Campbell AVW2xx Vibrating Wire Interfaces – MultiLogger Application Note #21 – Page 9 of 13
Use the following configuration for 4 multiplexer configuration:
Mux
Mux
Model
Gage Ty
pe
Channels
Wires
Enable
Clock
AVW2xx CH
1 As Req’d Vibrating Wire 16/32 4/2 C1 C4 (CR800)
C8 (CR1000)
1
2 As Req’d Vibrating Wire 16/32 4/2 C2 C4 (CR800)
C8 (CR1000)
1
3 As Req’d Vibrating Wire 16/32 4/2 C1 C4 (CR800)
C8 (CR1000)
2
4 As Req’d Vibrating Wire 16/32 4/2 C2 C4 (CR800)
C8 (CR1000)
2
Use the following configuration for 6 multiplexer configuration (CR1000 only):
Mux
Mux
Model
Gage Type
Channels
Wires
Enable
Clock
AVW2xx CH
1 As Req’d Vibrating Wire 16/32 4/2 C1 C8 1
2 As Req’d Vibrating Wire 16/32 4/2 C2 C8 1
3 As Req’d Vibrating Wire 16/32 4/2 C3 C8 1
4 As Req’d Vibrating Wire 16/32 4/2 C1 C8 2
5 As Req’d Vibrating Wire 16/32 4/2 C2 C8 2
6 As Req’d Vibrating Wire 16/32 4/2 C3 C8 2
Use the following configuration for 8 multiplexer configuration (CR1000 only):
Mux
Mux
Model
Gage Type
Channels
Wires
Enable
Clock
AVW2xx CH
1 As Req’d Vibrating Wire 16/32 4/2 C1 C8 1
2 As Req’d Vibrating Wire 16/32 4/2 C2 C8 1
3 As Req’d Vibrating Wire 16/32 4/2 C3 C8 1
4 As Req’d Vibrating Wire 16/32 4/2 C4 C8 1
5 As Req’d Vibrating Wire 16/32 4/2 C1 C8 2
6 As Req’d Vibrating Wire 16/32 4/2 C2 C8 2
7 As Req’d Vibrating Wire 16/32 4/2 C3 C8 2
8 As Req’d Vibrating Wire 16/32 4/2 C4 C8 2
Use the following configuration for 10 multiplexer configuration (CR1000 only):
Mux
Mux
Model
Gage Type
Channels
Wires
Enable
Clock
AVW2xx CH
1 As Req’d Vibrating Wire 16/32 4/2 C1 C8 1
2 As Req’d Vibrating Wire 16/32 4/2 C2 C8 1
3 As Req’d Vibrating Wire 16/32 4/2 C3 C8 1
4 As Req’d Vibrating Wire 16/32 4/2 C4 C8 1
5 As Req’d Vibrating Wire 16/32 4/2 C5 C8 1
6 As Req’d Vibrating Wire 16/32 4/2 C1 C8 2
7 As Req’d Vibrating Wire 16/32 4/2 C2 C8 2
8 As Req’d Vibrating Wire 16/32 4/2 C3 C8 2
9 As Req’d Vibrating Wire 16/32 4/2 C4 C8 2
10 As Req’d Vibrating Wire 16/32 4/2 C5 C8 2
Note: Use the same gage types for Channel Configuration as shown in Direct Connect Section. Be
sure to use appropriate Channel type to match multiplexer to AVW2xx wiring.