Campbell CR800 Spécifications Page 31

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 324
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 30
CR800 and CR850 Overview
OV4.4.1 Creating a CR800 Program using Short Cut
Objective: Every one second, measure air temperature in degrees C with a
Type T thermocouple, and store one-minute average Battery Voltage, Panel
Temperature, and Thermocouple temperature.
A Type T Thermocouple is included with CR800, packaged with
the screwdriver. The thermocouple consists of a pair of
5-inch wires with blue/red insulation, soldered together at one
end.
NOTE
Click on the Short Cut button to display the Home screen, as shown below.
Each of the four steps has a button with a ? for accessing Help. Use the Help
in conjunction with the steps outlined below:
Step 1: Create a New File
Step 1 is to open a new or existing file. From the Home page, click the New
button. Use the drop-down list box to select the CR800. Enter a 1 second
Scan Interval and click OK to complete Step 1.
Step 2: Select the Sensors
A Type T thermocouple consists of two wires of dissimilar metals (copper and
constantan) soldered together at one end. The soldered end is the measurement
junction; the junction that is created when the thermocouple is wired to the
CR800 is the reference junction.
When the two junctions are at different temperatures, a voltage proportional to
the temperature difference is induced into the wires. The thermocouple
measurement requires the reference junction temperature to calculate the
measurement junction temperature.