CS225 Temperature String
20
Figure 72 Screen capture of SDI-12 Transparent Mode on
CRBasic CR800 Datalogger using control port 1 and prompting for
SDI-12 addresses
6. To change the SDI-12 address, press the <enter> key. At the “CR800>
”CR1000>” prompt enter the command SDI-12 and press the <enter> key.
Enter the appropriate control port, press the <enter> key, and enter aAb!;
where a is the current address from the above step and b is the new
address. The temperature sensor will change its address and the datalogger
will respond with the new address and then exit the SDI-12 Transparent
Mode.