User Guide
7
Table 3. Power Connections using PSW12 Peripherals
HMP45C PSW12 Peripheral Datalogger
Description Colour Terminal
Wire
Power Red 12V Red 12V
Power Ground Black G Black* See tables
1 & 2
Yellow Control Port
*The black wire of the PSW12 should be connected to the type of datalogger
ground channel recommended for the HMP45C black wire as listed in Table 1
and 2.
5. Example Programs
This section is for users who write their own datalogger programs. A datalogger
program to measure this sensor can be created using Campbell Scientific’s Short
Cut Program Builder software. You do not need to read this section to use Short
Cut.
The temperature and relative humidity signals from the HMP45C can be
measured using a single-ended analogue measurement or a differential analogue
measurement.
Use a single-ended analogue measurement when the HMP45C signal lead length
is less than 6.1 m (20 ft.) or if the probe will be turned on and off under
datalogger control between measurements. For lead lengths greater than 6.1 m
(20 ft.) or when the probe will be continuously powered, use a differential
analogue measurement. For a discussion on errors caused by long lead lengths
see Section 6.
The HMP45C output scale is 0 to 1000 millivolts for the temperature range of
-40°C to +60°C and for the relative humidity range of 0 to 100%. Tables 4 and 5
provide calibration information for temperature and relative humidity.
Table 4. Calibration for Temperature
Units Multiplier
(degrees mV
-1
)
Offset
(degrees)
Celsius 0.1 -40
Fahrenheit 0.18 -40
Table 5. Calibration for Relative Humidity
Units Multiplier
(% mV
-1
)
Offset
(%)
Percent 0.1 0
Fraction 0.001 0