AM16/32B Relay Analog Multiplexer
Delay (0,20,mSec)
Portset (2,0) ‘Set port 2 low
INCREMENT INDEX AND MEASURE
I=I+1
'User specified measurement instruction
‘Storing results in Variable(I)
END MEASUREMENT LOOP
NextSubScan
DEACTIVATE MULTIPLEXER
Portset (1 ,0) 'Set C1 Low to disable Multiplexer
In addition to precision voltage excitation, the CR5000 and CR3000 have
programmable current excitation. Current excitation allows a resistance
measurement on a four-wire sensor (e.g., a PRT) such as shown in Figure 15
using only a single differential channel and no fixed resistor; the excitation
return goes directly to ground. With the current excitation the resistance of the
relays and lead wire do not affect the measurement.
5.1.1 CR1000, CR800, and CR850 Programming
Although the following example is a CR1000 program, a similar program can
be used for the CR800 or CR850. This CR1000 program uses the AM16/32B
to measure 48 CS616 probes connected in the 4x16 configuration. The
program also measures datalogger battery voltage and temperature.
14