Vue de la page 15
CS115 Barometric Pressure Sensor
12
5.2 Pulse Count Measurement Example
5.2.1 Pulse Count Measurement Example for 21X
EXAMPLE 5. Sample Program for 21X
;{21X}
;
*Table 1 Program
01: 1 Execution Interval (seconds)
1: If time is (P92)
1: 59 Minutes into a
2: 60 Minute Interval
3: 46* Set Port 6* High
2: If time is (P92)
1: 0 Minutes into a
2: 60 Minute Interval
3: 30 Then Do
3: Pulse (P3)
1: 1 Reps
2: 1* Pulse Input Channel
3: 24 Low Level AC, 16 Bit, Output Hz
4: 1* Loc [ P_mb ]
5: 1 Mult
6: 0.0 Offset
4: Do (P86)
1: 56* Set Port 6* Low
5: End (P95)
6: If time is (P92)
1: 0 Minutes into a
2: 60 Minute Interval
3: 10 Set Output Flag High
7: Real Time (P77)
1: 0110 Day,Hour/Minute (midnight = 0000)
8: Resolution (P78)
1: 1 High Resolution
9: Sample (P70)
1: 1 Reps
2: 1 Loc [ P_mb ]
*Table 2 Program
02: 0.0000 Execution Interval (seconds)