Raven XT-Rogers Sierra Wireless Cellular Modem
7.3 LoggerNet/PC400W Device Map
Check your LoggerNet setup.
a. Make sure the port number at the end of the IP address matches the port
number of the Raven (e.g. 6785, see Figure 7.3-1).
FIGURE 7.3-1. Device Port Configuration
b. Try adding a few seconds to the extra response time on the IP Port in
LoggerNet (you should not need more than 5 seconds).
c. If you are trying to communicate to a PakBus datalogger:
i. Verify the PakBus address in the setup screen matches that of the
datalogger.
ii. If you have multiple PakBus networks/ports setup in LoggerNet,
uncheck the ‘PakBus Port Always Open’ options on all PakBus ports.