Figure 4 illustrates the DIP switch SW2 for switching between a GK-403 or Datalogger
application. “DATALOGGER”” is the default SW2 position:
Figure 4 – GK-403/DATALOGGER Selection
MICRO-1000 / 800 (CR1000 / CR800) Mode of Operation
The MICRO-800 and MICRO-1000 (which respectively utilize a CR800 and CR1000
controller, manufactured by Campbell Scientific, Inc. of Logan, Utah) mode of operation
uses two control lines to operate the multiplexer. The RESET line enables the
multiplexer and activates the MICRO-800/MICRO-1000 mode of clocking. Pulses
received on the CLOCK line sequentially increment the channels while the RESET line is
held high. See the timing diagram below;
The CLOCK line sequentially advances the channels beginning with channel 1. Note the
timing diagrams below for 16 and 32 channel switching, respectively.
Reset
Clock
Channel 1
T1
T2
T3
No Channel
Selected
No Channel
Selected
Channel 16
Pulse 1
Pulse 2
Pulse 31
Timing:
T2 = 2 mSsec(min)
T3 = 2
mSsec(min)
T1 = 50 mSec(min.)
Selected
Selected
Pulse 32
Figure 7 - 16 Channel MICRO-800/MICRO-1000 Channel Selection Timing
GK-403
DATALOGGER
SW2