Campbell CR200 Manuel de l'opérateur Page 58

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 210
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 57
Section 4. Sensor Support
FIGURE. Pulse Input Types (p. 7) illustrates pulse input types measured by the
CR200(X). Dedicated pulse input channel P_SW can be configured to read
high- frequency pulses or switch closure, while P_LL can be configured to read
a low-level AC signal. With a 100 kOhm pull-up resistor added to the wiring
panel P_LL, C1, or C2 can measure pulse input signals (See Pulse Input (P_SW
p. 44).
Figure 30: Pulse Input Types
4.4.1.1 Pulse Input (P_SW)
Internal hardware routes high-frequency pulse to an inverting CMOS input
buffer with input hysteresis. The CMOS input buffer is guaranteed to be an
output zero level with its input ≥ 2.7 V, and guaranteed to be an output one with
its input ≤ 0.9 V. An RC input filter with approximately a 1 µs time constant
precedes the inverting CMOS input buffer, resulting in an amplitude reduction
of high frequency signals between the P_SW terminal block and the inverting
CMOS input buffer as illustrated in FIGURE. Amplitude reduction of pulse-
count waveform. For a 0 to 5 Volt square wave applied to P_SW, the maximum
frequency that can be counted in pulse input mode is approximately 1 kHz.
Figure 31: Amplitude Reduction of Pulse-Count Waveform (before and
after 1 ms time constant filter)
44
Vue de la page 57
1 2 ... 53 54 55 56 57 58 59 60 61 62 63 ... 209 210

Commentaires sur ces manuels

Pas de commentaire