Installation, Operation and Maintainance of Automatic Meteorological Stations
The CS500 is powered by the CR10X 12V peripheral power terminal and draws about 2 mA current while active. To
conserve energy, the datalogger is programmed to deactivate the CS500 when the probe is not measuring.
For detailed specifications, the reader is referred to corresponding Campbell Scientific Instruction Manual for the
CS500 Temperature and Relative Humidity Probe.
3.4.2 Installation
The CS500 must be housed inside a solar radiation shield. Clamp the radiation shield to the tripod mast as shown in
figure 11. Remove the yellow protection cap, place the CS500 into the radiation shield, and fix it with the mounting
clamp. Keep the yellow protection cap for future shipping and storage.
Sensors
Figure 11: Radiation Shield for the CS500 Temperature & RH Sensor
Attach the CS500 cable to the wiring panel of the CR10X logger according to the wiring diagram in table 1 in para-
graph 2.2, and Annex 2, as follows:
- black wire to terminal H1;
- clear wire to G terminal left of H1;
- brown wire to terminal L1;
- green wire to AG terminal right of L1;
- red wire to terminal SW 12V;