PakBus Networking Guide
15
Step 12 – LoggerNet Connect to Dataloggers
a. Highlight the CR10XPB_1 device in LoggerNet Connect Screen’s Station
window.
b. Click the Connect button.
c. Open Status Monitor on the LoggerNet Toolbar and highlight ComPort_1.
Click View I/O and size/position the Low Level Log window to view I/O
occurring between LoggerNet and the CR10XPB.
On the left of the window the “T”s represent data LoggerNet transmitted
and the “R”s represent data LoggerNet has received. Notice that the
PakBus packets begin and end with a “BD”. A constant stream of Clock
Check/Set Command and Clock Check/Set Response packets (03 and 83,
see 9
th
hex digit pair beyond starting ‘bd”) will appear unless the “Pause
Clock Update” box is checked.
FIGURE 10. LoggerNet Low Level Log
d. In Connect Screen, Disconnect from CR10XPB_1 and highlight
CR205_2.
e. Click the Connect button.
f. Update table definitions in Setup by highlighting CR205_2, clicking the
Data Files tab, and clicking on the Get Table Definitions button. After a
few seconds the message, “Received table definitions for CR205_2” will
appear.
g. Set up a Numeric Display to view CR205_2 variable values. Click on
Connect Screen\Data Displays\Numeric button “1”. A Numeric Display
window should now be open. Click the Add button. In the Add Selection
window highlight “Public.” The public variables for the CR205_2
program will be listed in the right-hand panel. Highlight them and Paste
them to the Numeric Display. You should now see: RecNum, TimeStamp,