Campbell RF410 Manuel d'instructions Page 8

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 124
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 7
PakBus Networking Guide
2
2. Quick Start – A Basic PakBus Network
Ingredients of a PakBus Network
LoggerNet (server).
PakBus devices (dataloggers with PakBus OS or native PakBus devices
such as the CR200 Series).
Routers (if used; typically dataloggers with PakBus OS and configured as
routers).
Communication peripherals (RF400 Series, COM210, COM310, NL100,
etc.).
Setup of a PakBus Network
Create the device map in LoggerNet.
Assign each PakBus device a unique address from 1 to 3999 (LoggerNet
defaults to address 4094).
Create datalogger-routers by entering *D15 settings for: max network
nodes, max device neighbors, max network routers.
Configure routers to discover by neighbor filter or by beaconing the next
device (neighbor) toward the destination.
Router configuration can be done with keyboard display using *D15 or by
sending a *.dld program with network settings having been configured in
Edlog \ Options \ PakBus Settings.
Set up communication peripheral interfaces to match the attached
datalogger’s beacon or neighbor filter port.
Set up all network RF400 Series radios with the same: hopping sequence,
network address, radio address and, normally, with standby mode of “< 24
mA always on” and Active Interface of “CSDC 7” (AutoSense if
connecting to a PC).
Vue de la page 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 123 124

Commentaires sur ces manuels

Pas de commentaire